Questions
Question 1
Determine if the light bulb will de-energize for each of the following breaks in the circuit. Consider just
one break at a time:
F
D
A
B
– E
+
C
• Choose one option for each point:
• A: de-energize / no effect
• B: de-energize / no effect
• C: de-energize / no effect
• D: de-energize / no effect
• E: de-energize / no effect
• F: de-energize / no effect
file 00002
2
Question 2
Examine the following illustration of a simple battery-switch-lamp circuit, connected together using
screw-terminal blocks, each connection point on each terminal block identified by a unique number:
+
–
Light bulb
1 2 3 4
Battery
Terminal block
9 10 11 12
5 Terminal block
6
7 Switch
8
Terminal block
Determinewhetherornotvoltageshouldbepresentbetweenthefollowingpairsofterminalblockpoints
with the switch in the ON position:
• Points 1 and 5:
• Points 6 and 7:
• Points 4 and 10:
• Points 9 and 12:
• Points 6 and 12:
• Points 9 and 10:
• Points 4 and 7:
Now, determine whether or not voltage should be present between the following pairs of terminal block
points with the switch in the OFF position:
• Points 1 and 5:
• Points 6 and 7:
• Points 4 and 10:
• Points 9 and 12:
• Points 6 and 12:
• Points 9 and 10:
• Points 4 and 7:
file 03302
3
9 | 1 |
5 |
6 |
7 |
8 |
Question 3
The following battery-switch-lamp circuit has a problem. Over time, corrosion has developed between
the wire end and the screw terminal labeled ”4” on the upper side of the top terminal block. This corroded
connectionnowhasahighresistanceinsteadofalowresistanceasitshould. Asaresult, thelightbulbdoes
not energize when the switch is turned ON:
+
–
Corroded
connection
Light bulb
1 2 3 4
Battery
Terminal block
9 10 11 12
5 Terminal block
6
7 Switch
8
Terminal block
Taking voltage measurements with a voltmeter, how do you think this corrosion problem will reveal
itself with the switch on the ON position? In other words, which voltage measurement in this circuit (i.e.
between which pair or pairs of terminal block points) will be unusual as a result of the bad connection at
point #4, and approximately how much voltage should that measurement be?
file 03303
4
9 | 1 |
5 |
6 |
7 |
8 |
Question 4
In this battery-switch-lamp circuit, the metal filament wire inside the lamp has burned up, so that it
no longer forms an electrically continuous connection. In other words, the filament has failed ”open.”
+
–
Filament burned open
Light bulb
1 2 3 4
Battery
Terminal block
9 10 11 12
5 Terminal block
6
7 Switch
8
Terminal block
Of course, this means the lamp will not turn on, no matter what is done with the switch. It also means
that most of the voltage measurements taken in the circuit will be the same as with a properly operating
circuit. Thereis,however,onevoltagemeasurementwhichwillbedifferentinthecircuitwiththeburned-out
filamentthaninaproperlyworkingcircuit. Identifywhatpairorpairsofterminalblockpointsthisdifferent
voltage will be measured between, what switch state (ON or OFF) it will appear in, and what this different
voltage measurement will actually be relative to the battery voltage.
file 03304
Question 5
In this circuit, where would you expect to measure full battery voltage (between what pairs of test
points)?
A B C D E
F G H I J
file 00119
5
5 |
6 |
7 |
8 |
Question 6
In this circuit, where would you not expect to measure significant voltage (between what pairs of test
points)?
A B C D E
F G H I J
file 00120
Question 7
Suppose this battery and light bulb circuit failed to work. Using nothing but a voltmeter, how would
you check the circuit to determine where the problem is located? Note: the letters indicate ”test points”
along the wiring where you may probe with the circuit with your voltmeter.
A B C D E
F G H I J
file 00118
Question 8
Suppose this battery and light bulb circuit failed to work:
A B C D E
–
V
+
F G H I J
Using a voltmeter, a technician measures full battery voltage between the points C and H. What does
this single measurement indicate about the condition of the circuit? Be as specific as you can.
file 00122
6
Question 9
Suppose this battery and light bulb circuit failed to work:
A B C D E
–
V
+
F G H I J
Usingavoltmeter, atechnicianmeasuresfullbatteryvoltagebetweenthepointsCandH.Theresultof
this single measurement indicates which half of the circuit there is a definite problem in. What would you
recommend as the next voltmeter measurement to take in troubleshooting the circuit, following the same
”divide in half” strategy?
file 00124
Question 10
Suppose this battery and light bulb circuit failed to work:
A B C D E
–
V
+
F G H I J
Using a voltmeter, a technician measures 0 volts between the points C and H. What does this single
measurement indicate about the condition of the circuit? Be as specific as you can.
file 00123
Question 11
Suppose this battery and light bulb circuit failed to work:
A B C D E
–
V
+
F G H I J
Using a voltmeter, a technician measures 0 volts between the points C and H. The result of this single
measurement indicates which half of the circuit there is a definite problem in. What would you recommend
asthenextvoltmetermeasurementtotakeintroubleshootingthecircuit,followingthesame”divideinhalf”
strategy?
file 00125
7
Question 12
Suppose this battery and light bulb circuit failed to work:
A B C D E
F G H I J
Using nothing but a voltmeter, a technician measures voltage between the following sets of points:
• Between A and C: 0 volts
• Between D and G: 12 volts
• Between E and J: 0 volts
• Between B and E: 12 volts
From these voltage measurements, what can you tell about the condition of the battery, wiring, and
light bulb? Be as specific as you can.
Challenge question: identify which of the four measurement are unnecessary in determining the precise
location of the fault in this circuit.
file 00121
Question 13
The circuit shown here is called a ”bridge rectifier,” and its purpose is to convert alternating current
(from the ”power-supply” unit) into direct current. Suppose you were instructed to check the continuity of
the switch (SW1) mounted on the printed circuit board. What would be a fast and effective way of testing
this switch’s continuity (ideally, without removing the switch from the circuit board)?
Low-voltage
AC power supply
12
6 6
D1 D2
R1
D3 D4 SW1
file 00100
8
Question 14
Identify which of these are true statements:
1. Between two points that are electrically common to each other, there is guaranteed to be zero voltage.
2. Ifzerovoltageismeasuredbetweentwopoints, thosepointsmustbeelectricallycommontoeachother.
3. Between two points that are not electrically common to each other, there is guaranteed to be voltage.
4. If voltage is measured between two points, those points must not be electrically common to each other.
file 00184
9
Question 15
Suppose a technician were troubleshooting the following circuit, whose light bulb refused to light up:
TB1
1 2 3 4
Low-voltage
AC power supply
12
6 6
1 2 3 4 TB2
The technician records their steps on a piece of paper divided into two columns: Observations, and
Conclusions, drawing a horizontal line underneath each conclusion after it is made:
Observations Conclusions
(What I measured, sensed, or did) (What I think)
Turned switch ON — no light. Definitely a problem in this circuit!
Measured 12 volts AC between terminals Power supply is functioning properly.
TB1-1 and TB2-1
Measured no voltage across the light bulb Light bulb is good, but just not receiving
(between TB2-2 and TB2-3) any power
Measured no voltage across switch
Switch is good
(between TB1-1 and TB1-3)
Measured 12 volts AC between terminals
TB2-1 and TB2-3
Measured 12 volts AC between terminals Wire between TB1-3 and TB2-3 is good
TB1-3 and TB2-1
Measured 12 volts AC between terminals Bad connection between those two
TB2-1 and TB2-2 terminals. Possibly an open wire or
dirty connection between wire and
the terminal block.
Replaced wire between TB2-1 and TB2-2,
Problem solved.
and the light bulb now lights up!
Critique this technician’s troubleshooting job, noting any errors or unnecessary steps.
file 00185
10
Observations (What I measured, sensed, or did) | Conclusions (What I think) |
Turned switch ON — no light. | Definitely a problem in this circuit! |
Measured 12 volts AC between terminals TB1-1 and TB2-1 | Power supply is functioning properly. |
Measured no voltage across the light bulb (between TB2-2 and TB2-3) | Light bulb is good, but just not receiving any power |
Measured no voltage across switch (between TB1-1 and TB1-3) | Switch is good |
Measured 12 volts AC between terminals TB2-1 and TB2-3 Measured 12 volts AC between terminals TB1-3 and TB2-1 | Wire between TB1-3 and TB2-3 is good |
Measured 12 volts AC between terminals TB2-1 and TB2-2 | Bad connection between those two terminals. Possibly an open wire or dirty connection between wire and the terminal block. |
Replaced wire between TB2-1 and TB2-2, and the light bulb now lights up! | Problem solved. |
Question 16
The following circuit has a problem. When the switch is closed, the lamp does not turn on:
Switch
Battery
Lamp
Identify which of these hypothetical faults could account for this problem, and which could not account
for the problem. In other words, which of these faults are possible, and which are not possible, given the
symptoms exhibited by the circuit? Consider each of these hypothetical faults one at a time (no multiple,
simultaneous faults):
• Light bulb filament failed open
• Switch failed shorted
• Switch failed open
file 03297
Question 17
The following circuit has a problem. Switch #1 is able to control lamp #1, but lamp #2 never comes
on no matter what is done with switch #2:
TP1 TP2 TP3
Switch #1 Switch #2
Battery
Lamp #1 Lamp #2
TP4 TP5 TP6
Identify which of these hypothetical faults could account for this problem, and which could not account
for the problem. In other words, which of these faults are possible, and which are not possible, given the
symptoms exhibited by the circuit? Consider each of these hypothetical faults one at a time (no multiple,
simultaneous faults):
• Battery is dead
• Switch #2 failed open
• Switch #2 failed shorted
• Switch #1 failed open
• Switch #1 failed shorted
• Open wire between test points 1 and 2 (between TP1 and TP2)
• Open wire between test points 5 and 6 (between TP5 and TP6)
file 03298
11
Question 18
The following circuit has a problem. Switch #2 is able to control lamp #2, but lamp #1 never comes
on no matter what is done with switch #1:
TP1 TP2 TP3
Switch #1 Switch #2
Battery
Lamp #1 Lamp #2
TP4 TP5 TP6
Identify which of these hypothetical faults could account for this problem, and which could not account
for the problem. In other words, which of these faults are possible, and which are not possible, given the
symptoms exhibited by the circuit? Consider each of these hypothetical faults one at a time (no multiple,
simultaneous faults):
• Battery is dead
• Lamp #1 filament failed open
• Lamp #2 filament failed open
• Switch #2 failed open
• Switch #2 failed shorted
• Switch #1 failed open
• Switch #1 failed shorted
• Open wire between test points 1 and 2 (between TP1 and TP2)
• Open wire between test points 4 and 5 (between TP4 and TP5)
• Open wire between test points 5 and 6 (between TP5 and TP6)
file 03299
12
Answers
Answer 1
• A: de-energize
• B: no effect
• C: no effect
• D: no effect
• E: de-energize
• F: no effect
Answer 2
Switch ON:
• Points 1 and 5: Voltage!
• Points 6 and 7: No voltage
• Points 4 and 10: No voltage
• Points 9 and 12: Voltage!
• Points 6 and 12: No voltage
• Points 9 and 10: No voltage
• Points 4 and 7: Voltage!
Switch OFF:
• Points 1 and 5: Voltage!
• Points 6 and 7: No voltage
• Points 4 and 10: No voltage
• Points 9 and 12: No voltage
• Points 6 and 12: Voltage!
• Points 9 and 10: No voltage
• Points 4 and 7: Voltage!
Follow-upquestion: explainwhytherewillbevoltageornovoltagebetweeneachofthesepairsofpoints
for the two circuit conditions (switch on and switch off).
Answer 3
With the corroded connection at terminal #4, the following voltage measurements should read
abnormallyhigh(almostfullbatteryvoltage, whereastheyshouldregisterzerovoltsifallconnectionsinthe
circuit are good):
• Points 1 and 4
• Points 1 and 9
• Points 1 and 10
Follow-up question: there are also several voltage measurements in this faulty circuit that will read
abnormally low as a result of the corroded connection at point #4. Identify which pairs of points the
abnormally low voltage will be measured between.
Answer 4
With the filament burned open, the only voltage measurement that will change in the circuit is the
voltage across the switch when it is in the OFF state. Normally, the voltage across the switch in the OFF
state will be full battery voltage, but now (with the open filament) it will be zero. I will let you determine
which points in the circuit you may measure switch voltage between.
13
Answer 5
You should expect to measure full battery voltage with one test lead of your voltmeter touching any of
the points along the top wire of the circuit (points A through E), and with the other test lead touching any
of the points along the bottom wire of the circuit (points F through J).
Answer 6
You should not measure any significant voltage between any of the test points along the upper wire (A
to B, A to C, A to D, etc.), nor between any of the test points along the lower wire (F to G, F to H, F to
I, etc.). As a general rule, points in a circuit that are electrically common to each other should never have
voltage between them.
Answer 7
There are several strategies which may be employed to find the location of the problem in this circuit.
One popular technique is to ”divide the circuit in half” by testing for voltage between points C and H first.
The presence of absence of voltage between these two points will indicate whether the problem lies between
those points and the battery, or between those points and the light bulb (assuming there is but a single
problem in the circuit – a large assumption!).
Answer 8
Based on this one measurement, we are able to determine that the battery is outputting full voltage,
andthatthecircuitwiringiscontinuousfromthenegativebatteryterminaltopointC,andfromthepositive
battery terminal to point H. The fault is an ”open” somewhere to the right of points C and H – possibly
more than one.
Answer 9
To ”divide the circuit in half” again, measure voltage between points D and I.
Answer 10
Basedonthisonemeasurement,weareabletodeterminethatthereisdefinitelyaprobleminthecircuit
somewhere on the left-hand side (from points C and H, left). The exact nature of the problem is unknown,
but there is definitely a problem of some nature in that half of the circuit.
There may or may not be a problem on the right-hand side of the circuit, as well. Given this single
voltage measurement, we simply cannot tell.
Answer 11
To ”divide the circuit in half” again, measure voltage between points B and G.
Answer 12
Based on these measurements, we are able to determine that the battery’s voltage is 12 volts, that the
light bulb has good continuity, and that there is a single break in the circuit between points D and E.
Challenge answer: the two ”0 volt” measurements are unnecessary in determining the location of the
fault in this circuit.
Answer 13
Disconnect the power supply from the circuit board (only one wire need be disconnected), and then use
an ohmmeter to measure continuity across the switch terminals when in the ”ON” position and when in the
”OFF” position. Incidentally, this is not the only way to check the switch’s continuity, but it is the most
direct.
14
Answer 14
Only two out of the four given statements are true:
1. Between two points that are electrically common to each other, there is guaranteed to be zero voltage.
4. If voltage is measured between two points, those points must not be electrically common to each other.
For those having difficultly understanding this, test the following statements for truth. Each of these
statements follows the same logical pattern of electrical statements given at the beginning of this question:
1. All rabbits are mammals.
2. All mammals are rabbits.
3. All non-rabbits are non-mammals.
4. All non-mammals are non-rabbits.
Answer 15
The first step and conclusion, while seemingly unnecessary, are actually good to check. Just because
someone tells you there is a problem with a circuit does not necessarily mean there is a problem with it.
People can make mistakes, and it is usually a good idea to verify the nature of the problem with a system
before troubleshooting.
Thesecondconclusion(”Powersupplyisfunctioningproperly”)isunderstated. Inactuality,thepresence
of voltage between these two points proves that not only is the power supply functioning properly, but both
wires between the power supply and terminals TB1-1 and TB2-1 have good continuity, and the connections
between the wires and their respective terminals are good as well. This eliminates several portions of the
circuit as being problematic.
Checking for voltage across the light bulb terminals is a good step, but the lack of voltage does not
prove the light bulb is not failed! All it means is that there is some other problem between the light bulb
and the last two connections where voltage was measured (between TB1-1 and TB2-1). For all we know at
this point, the light bulb could be failed as well as there being a failure somewhere else in the circuit.
Checkingforvoltageacrosstheswitchisanothergoodstep,butthelackofvoltagetheredoesnotprove
that the switch has good continuity, any more than a lack of voltage proved the light bulb’s filament had
good continuity either. There still could be multiple ”opens” in this circuit.
The presence of voltage between TB2-1 and TB2-3 narrows the possibility of failure in the circuit quite
abit. KnowingthatthereisvoltagebetweenthesetwoterminalsprovesthereisgoodcontinuityfromTB2-3
to TB1-3, through the switch, and all the way back to the power supply. From step 2 we already know
there is good continuity from TB2-1 back to the power supply as well. This conclusively tells us that the
problem(s) must lie between TB2-1 and TB2-3.
It is a wasted step to check for voltage between TB1-3 and TB2-1.
The measurement of voltage between TB2-1 and TB2-2 proves the location of the failure: an ”open”
between those two points. It also proves that there are no other ”open” failures in the circuit.
The final step documenting replacement of the wire between TB2-1 and TB2-2, while not essential,
is not really wasted, either. Troubleshooting journals such as this are helpful when searching for complex
problems in large systems, where more than one person may have to work on finding the problem(s). If
there is more than one failure in a system, it is helpful to document the repair for the benefit of anyone else
working on solving the problem later!
Answer 16
• Light bulb filament failed open: Possible
• Switch failed shorted: Not possible
• Switch failed open: Possible
Follow-up question: if we allow ourselves to consider more than one fault occurring at the same time,
does the ”switch failed shorted” scenario become possible? Explain why or why not.
15
Answer 17
• Battery is dead: Not possible
• Switch #2 failed open: Possible
• Switch #2 failed shorted: Not possible
• Switch #1 failed open: Not possible
• Switch #1 failed shorted: Not possible
• Open wire between test points 1 and 2 (between TP1 and TP2): Not possible
• Open wire between test points 5 and 6 (between TP5 and TP6): Possible
Follow-up question: if we allow ourselves to consider more than one fault occurring at the same time,
which of these scenarios becomes possible? Explain why.
Answer 18
• Battery is dead: Not possible
• Lamp #1 filament failed open: Possible
• Lamp #2 filament failed open: Not possible
• Switch #2 failed open: Not possible
• Switch #2 failed shorted: Not possible
• Switch #1 failed open: Possible
• Switch #1 failed shorted: Not possible
• Open wire between test points 1 and 2 (between TP1 and TP2): Not possible
• Open wire between test points 4 and 5 (between TP4 and TP5): Not possible
• Open wire between test points 5 and 6 (between TP5 and TP6): Not possible
Follow-up question: if we allow ourselves to consider more than one fault occurring at the same time,
which of these scenarios becomes possible? Explain why.
16
Notes
Notes 1
This question is an important one in the students’ process of learning troubleshooting. Emphasize the
importanceofinductivethinking: derivinggeneralprinciplesfromspecificinstances. Whatdoesthebehavior
of this circuit tell us about electrical continuity?
Notes 2
This question is not really a troubleshooting question per se, but the principles involved in successfully
determining the presence or absence of voltage are critically important to being able to troubleshoot simple
circuits using a voltmeter.
I have found that the concept of electrically common points is most helpful when students first learn
to relate voltage drop with continuity (breaks or non-breaks) in a circuit. You might want them to identify
which points in this circuit are electrically common to one another (in either or both switch positions).
Notes 3
Explain to your students what environmental factors contribute to corrosion (water, acids, caustics,
etc.) and how a corroded electrical connection is usually not equivalent to a complete ”open” break in a
circuit. Quiteoftenacorrodedconnectionisasubstantialresistanceofunstablevalue,leadingtointermittent
problems in the circuit.
Notes 4
Be sure to ask your students why they think there will be no voltage dropped across the switch when
it is OFF, now that the filament has burned open. It may be helpful to draw a schematic diagram (without
all the terminal block points shown) as you discuss the reasoning with your students.
Notes 5
This circuit provides an excellent opportunity to discuss the concept of ”electrically common” points.
Any points in a circuit directly connected together with wire are considered ”electrically common” to each
other: a voltage measurement referenced at any one of those points should be identical if referenced any of
the other points as well.
Notes 6
The answer uses a concept which I’ve found to be very helpful in understanding electrical circuits: the
idea of points in a circuit being electrically common to each other. Simply put, this means the points are
connectedtogetherbyconductorsofnegligibleresistance. Havingnearly0ohmsofresistancebetweenpoints
assures insignificant voltage drop, even for large currents.
Conversely, if significant voltage is measured between points in a circuit, you can be assured that
those points are not electrically common to each other. Engage your students in a discussion of electrical
commonality and expected voltage drops:
• If voltage is measured between two points in a circuit, are those two points electrically common to each
other? Why or why not?
• If no voltage is measured between two points in a circuit, are those two points electrically common to
each other? Why or why not?
17
Notes 7
A circuit like this is very easy to construct, and makes for an excellent classroom demonstration piece.
I’ve used such a circuit, constructed on a piece of pegboard 2 feet by 4 feet, with metal screws acting as test
points, for students to develop their troubleshooting skills in front of the class where everyone may observe
and learn together.
It has been my experience that students who experience difficulty troubleshooting circuits in general
usually experience difficulty troubleshooting this simple circuit in particular. Although the circuit itself
couldn’t be simpler, the fundamental concept of voltage as a quantity measurable only between 2 points is
confusing for many. Spending lots of time learning to troubleshoot a circuit such as this will be greatly
beneficial in the future!
Notes 8
Some measurements given definite answers, while others only indefinite answers. In this particular
question, the single voltage measurement tells us definite things about the left-hand side of the circuit, but
littleabouttheright-handside. Itisveryimportantforstudentstodevelopthelogicalskillofdistinguishing
necessary conclusions from possible conclusions in troubleshooting scenarios. A skill like this takes time and
practice to develop, so be sure to spend adequate time throughout the course with your students honing it!
Notes 9
Some troubleshooters refer to this strategy as ”divide and conquer,” because it divides the possibilities
of fault location by a factor of 2 with each step. Make sure your students understand that being able to
immediately determine which part of a system is not faulted is a valuable time-saver.
Notes 10
There are times when a voltmeter indication of 0 volts is just as informative concerning a circuit fault
as a non-zero measurement. In this case, the measurement tells us that a definite problem exists in one half
of the circuit.
Notes 11
Some troubleshooters refer to this strategy as ”divide and conquer,” because it divides the possibilities
of fault location by a factor of 2 with each step.
It is important to realize in situations such as this that no determination of faultlessness in the circuit
has been made yet. By measuring 0 volts between points C and H, we know there is a definite problem in
the left half of the circuit, but we have by no means ”cleared” the right half of the circuit of any fault. For
allweknow,theremaybefaultsinbothhalvesofthecircuit! Onlyfurtherinvestigationwillrevealthetruth.
Notes 12
Scenarios such as this are excellent for group discussion, encouraging students to think critically about
the data and to apply their practical knowledge of electricity to a realistic problem.
Notes 13
Challengeyourstudentstothinkofothermethodswhichcouldbeusedtochecktheswitch’scontinuity.
Thereisoftenmorethanonewaytoperformacertaincheckofcomponentfunction,ifyouareknowledgeable
in electrical theory and creative in your use of test equipment!
18
Notes 14
What we have here is an exercise in Aristotelian logic. In either scenario (points in a circuit, or
animals), statement 2 is the converse of statement 1, while statement 3 is the inverse and statement 4 is the
contrapositive. Only the contrapositive of a statement is guaranteed to share the same truth value as the
original statement.
This is no esoteric exercise. Rather, it is a hard-learned fact: many students mistakenly think that
because there is guaranteed to be no voltage between electrically common points in a circuit, then the
absence of voltage between two points must mean those two points are electrically common to each other!
This is not necessarily true, because situations exist where two points may not be electrically common, yet
still have no voltage between them. Electrical commonality is just one way that two points can have zero
voltage between them, not the only way!
The contrapositive of this rule, however, is a valuable troubleshooting tool: if there is substantial
voltage measured between two points in a circuit, then we know without a doubt that those two points are
not electrically common to each other!
Notes 15
Circuit troubleshooting is the highest level of thinking required of many electrical and electronics
professionals: toidentifyfaultsefficientlybasedonaknowledgeoffundamentalprinciplesandtestequipment
usage. Good troubleshooters are rare, and in my opinion that has more to do with the lack of effective
technical education than it does a lack of natural ability.
It is not enough to merely tell students what they should do in troubleshooting, or to give them easy-
to-follow steps. Students must be placed in scenarios where they are required to think their way through to
a solution. Fortunately, electrical circuit troubleshooting is an activity that works well for small groups of
students to engage in as well as individual students. A ”virtual” troubleshooting exercise such as this one is
a good way to start students thinking in the right ways to becoming effective troubleshooters.
Notes 16
This question helps students build the skill of eliminating unlikely fault possibilities, allowing them to
concentrate instead on what is more likely. An important skill in system troubleshooting is the ability to
formulate probabilities for various fault scenarios. Without thisskill, you will waste a lot of time looking for
unlikely faults, thereby wasting time.
For each fault scenario it is important to ask your studentswhythey think it is possible or not possible.
It might be that some students get the right answer(s) for the wrong reasons, so it is good to explore the
reasoning for each answer.
Notes 17
This question helps students build the skill of eliminating unlikely fault possibilities, allowing them to
concentrate instead on what is more likely. An important skill in system troubleshooting is the ability to
formulate probabilities for various fault scenarios. Without thisskill, you will waste a lot of time looking for
unlikely faults, thereby wasting time.
For each fault scenario it is important to ask your studentswhythey think it is possible or not possible.
It might be that some students get the right answer(s) for the wrong reasons, so it is good to explore the
reasoning for each answer.
19
Notes 18
This question helps students build the skill of eliminating unlikely fault possibilities, allowing them to
concentrate instead on what is more likely. An important skill in system troubleshooting is the ability to
formulate probabilities for various fault scenarios. Without thisskill, you will waste a lot of time looking for
unlikely faults, thereby wasting time.
For each fault scenario it is important to ask your studentswhythey think it is possible or not possible.
It might be that some students get the right answer(s) for the wrong reasons, so it is good to explore the
reasoning for each answer.
20